DRL10-100 Series Specification Model DRL10 DRL30 DRL60 DRL100 Input Input Voltage range V 85 - 264Vac, 120 - 373Vdc* Input Surge Voltage - 300Vac for 5s Input Frequency Hz 47 - 63 Input Current (110/230Vac) A 0.18 / 0.12 0.6 / 0.4 1.2 / 0.8 2.0 / 1.1 Inrush Current at 230Vac (typ) (Cold Start) A 40 50 60 60 Leakage Current - Not applicable Power Factor (115/230Vac) - 0.56 / 0.42 0.6 / 0.4 0.5 / 0.43 0.5 / 0.43 Harmonic Compliance - Meets IEC61000-3-2 Class A No Load Power Consumption W <0.3 <0.3 <0.5 <0.5 Hold Up Time (typ) at 115Vac Input ms 20 20 20 15 Efficiency - See model selector table Average Efficiency (1) % 76.8 83.6 >87 87 Conducted & Radiated EMI - EN55032-B Conducted, EN55032-A Radiated Immunity - See model selector table Insulation Class - Construction suitable for Class II installation Safety Agency Certifications - IEC/UL/CSA/EN 62368-1, 60950-1, UL508 Listed, UL1310 Class 2 (2), CE Mark Immunity Test Standard Test Level Criteria Notes ESD EN61000-4-2 3 A 8kV air discharge Radiated Susceptibility EN61000-4-3 3 A - Electrical Fast Transient Burst EN61000-4-4 4 A - Surge EN61000-4-5 3 A - Conducted Susceptibility EN61000-4-6 3 A - Magnetic fields EN61000-4-8 4 A - 0% for 1 cycle A - Voltage Dips and EN61000-4-11 40% for 10/12 cycles B - Input Interruptions Class 3 Industrial 70% for 25/30 cycles B - 80% for 250/300 cycles B - SEMI F47 Line Dip SEMI F47 - - > 200Vac input Specification Model DRL10 DRL30 DRL60 DRL100 Output Output Voltage Adjustment - See model selector table Switching Frequency (230Vac 100% Load) (3) kHz ~103.6 96.9 - 103.8 87 - 94 84.4 - 95.5 Line Regulation mV 12 - 15V Outputs: 120 24V Output: 240 Load Regulation mV 12 - 15V Outputs: 120 24V Output: 240 Ripple & Noise mV 12 - 15V Outputs: 120 24V Output: 240 Temperature Coefficient %/C <0.02 Minimum Load - No minimum load required Overcurrent Protection % >105 Hiccup mode with auto recovery Overvoltage Protection V See model selector table Overtemperature Protection - - Remote Sense - - Remote On/Off - - DC Good - - Indicators & Signals - Green LED indicates DC is OK Parallel Operation - Not available Series Operation - Possible, see installation manual 2 DRL10-100 Series