Power Supplies 4 Silver Line Series Single & Multi-Output Linears Specications Parameter Condition Limit Input 100/120/220/230/240 Input Voltage VAC Selectable Input Frequency 47-63 Hz Output Line Regulation for 10% change 0.05% Load Regulation for 50% change 0.05% 3.0 mV maximum Ripple Peak-to-Peak DC Output 5% Minimum LVD Adjustment Range UL 60950 E137632 All 5-Volt outputs include build-in OVP The Silver Line series follows the industry accepted Overvoltage as standard (setting is footprint for open frame, linear power supplies. Sola Protection 6.2 V 0.4 V) OVP is improves on this design by offering standard screw optionally available on terminal connections and optional covers for safety other types considerations. Transient at 50% Load Changes 50 msec. Response Time Overload Automatic current limit Features Protection foldback Easy-to-install screw terminal connections Available to compensate for output Cover options Remote Sensing 0.5 VDC voltage drop on Industry standard footprint selected models. Universal input and approvals (115/230 VAC) General Low noise, extremely quiet DC output. For noise Operating Derate to 40% at 0 to +50C Temperature Range +70C sensitive or analog circuitry. Fast transient response. Ideal for test applications. Storage -25C to +85C Temperature Range Built-in OVP on 5 V models and optional on Temperature 12, 15 and 24 V models 0.01% 0C Coefcient (Typical) Automatic resetting overload protection Stability After warm-up .5% Short circuit protected Vibration Method 514 Per MIL-STD-810C Two year warranty Shock Method 516 Per MIL-STD-810C For most system Linear power supplies applications they will Applications have inherently low EMI/RFI meet requirements of conducted and radiate Industrial control circuits and components FCC Class B and VDE noise levels 0871 for class B Instrumentation Cover Option Derate power by an additional 15% Drives Forced air. 20 CFM required for full rating Cooling CNC machinery Derate 30% without cooling Equipment for food industry Specications are typical. Load Regulation on outputs without Remote Microprocessor circuits Sense, .1% typical. Analog circuits Noise sensitive circuitry and sensors Visit our website at www.solaheviduty.com or contact Technical Services at (800) 377-4384 with any questions. 110Power Supplies 4 SL Series Selection Table Dimensions - inches (mm) Catalog Number Output 1 Output 2 Output 3 Case SLS-05-030-1T 5 V 3 A* A SLS-05-060-1T 5 V 6 A* B1 SLS-05-090-1T 5 V 9 A* C SLS-05-120-1T 5 V 12 A* I2 12 V 1.7 A or 1 SLS-12-017T A 15 V 1.5 A SLS-12-034T 12 V 3.4 A B1 SLS-12-051T 12 V 5.1 A C SLS-12-068T 12 V 6.8 A I2 SLS-15-045T 15 V 4.5 A C SLS-15-060T 15 V 6 A I2 Case A SLS-24-012T 24 V 1.2 A A SLS-24-024T 24 V 2.4 A B2 SLS-24-036T 24 V 3.6 A C SLS-24-048T 24 V 4.8 A I2 SLS-24-072T 24 V 7.2 A K SLS-24-120T 24 V 12.0 A L 12 V 1 A or 15 -12 V 1 A or 1 SLD-12-1010-12T H1 V .8 A -15 V .8 -12 V 1.8 12 V 1.8 A or 1 SLD-12-1818-12T A or -15 V D 15 V 1.5 A 1.5 A SLD-12-3434-12T 12 V 3.4 A -12 V 3.4 A I3 SLD-15-3030-15T 15 V 3 A -15 V 3 A I3 SLD-12-6034-05T 5 V 6 A* 12 V 3.4 A I1 SLD-12-3015-05T 5 V 3 A* 12 V 1.5 A C1 12 V .4 A or -12 V .4 A or 1 SLT12-20404-12T 5 V 2 A* H2 15 V .4 A -15 V .4 A Case B 12 V 1 A or -12 V 1 A 1 SLT12-31010-12T 5 V 3 A* F 15 V .8 A or -15 V .8 A 12 V 1 A or -12 V 1 A or 1 SLT12-61010-12T 5V 6 A* I4 15 V 1 A -15 V 1 A Cover Options -12 V 1.8 12 V 1.8 A or 1 SLT12-61818-12T 5V 6A* A or -15 V G2 15 V 1.5 A Catalog Catalog 1.5 A Description Description Number Number SLT24-30530-05T 5V 3A* -5 V .5 A* 24 V 3 A G1 SLCASA-CVR Cover for Case A SLCASG-CVR Cover for Cases G1 and G2 Over Voltage Protector (OVP) SLCASB-CVR Cover for Case B SLCASH-CVR Cover for Cases H1 and H2 SLCASC-CVR Cover for Case C SLCASI-CVR Cover for Cases I1, I2, I3 and I4 6.2 V to 34 V SLO-12-000-1 For Cases B through K J1 Adjustable 8 A SLCASC1-CVR Cover for Case C1 SLCASK-CVR Cover for Case K SLCASD-CVR Cover for Case D SLCASL-CVR Cover for Case L 6.2 V to 34 V For Case A or Cases B through K SLO-12-000-TB J2 SLCASF-CVR Cover for Case F Adjustable 8 A (when used with a cover) Note: Covers are sold separately . When used, derate the power supply by 15% of its Notes: rated value. * With Built-In OVP With Remote Sense (R.S.) 1 12/15 Volt models are factory set for 12 Volt operation. 15 Volt operation is eld adjustable. Visit our website at www.solaheviduty.com or Contact Technical Services at (800) 377-4384 with any questions. 111