Product data sheet LUCA12FU Characteristics TeSys U, standard control unit, class 10, 3 to 12 A, 110 to 220 V DC/AC Product availability: Stock - Normally stocked in distribution facility Main Range TeSys Product name TeSys U Device short name LUCA Product or component Standard control unit type Product specific applica- Basic protection requirements for motor starters: tion overload and short-circuit Product compatibility LUFC00 LUFN.. Utilisation category AC-44 AC-43 AC-41 Motor power kW 9 kW at 690 V AC 50/60 Hz 5.5 kW at 400...440 V AC 50/60 Hz 5.5 kW at 500 V AC 50/60 Hz Thermal protection ad- 3...12 A justment range Uc control circuit volt- 110...220 V DC age 110...240 V AC Thermal overload class Class 10 - frequency limit: 40...60 Hz - temperature compensation: -13...158 F (-25...70 C) - conforming to IEC 60947-6-2 Class 10 - frequency limit: 40...60 Hz - temperature compensation: -13...158 F (-25...70 C) - conforming to UL 508 Class 20 - frequency limit: 40...60 Hz - temperature compensation: -13...158 F (-25...70 C) - conforming to IEC 60947-6-2 Class 20 - frequency limit: 40...60 Hz - temperature compensation: -13...158 F (-25...70 C) - conforming to UL 508 Complementary Main function available Manual reset Protection against overload and short-circuit Earth fault protection Protection against phase failure and phase imbalance Mounting mode Plug-in Mounting location Front side Control circuit voltage limits 88...242 V DC circuit 110...220 V in operation 88...264 V AC circuit 110...240 V in operation Typical current consumption 25 mA at 110...240 V AC I rms sealed with LUB12 25 mA at 110...240 V AC I rms sealed with LUB32 280 mA at 110...220 V DC I maximum while closing with LUB12 280 mA at 110...220 V DC I maximum while closing with LUB32 280 mA at 110...240 V AC I maximum while closing with LUB12 280 mA at 110...240 V AC I maximum while closing with LUB32 35 mA at 110...220 V DC I rms sealed with LUB12 35 mA at 110...220 V DC I rms sealed with LUB32 Operating time 35 ms opening with LUB12 control circuit 35 ms opening with LUB32 control circuit 50 ms closing with LUB12 control circuit 50 ms closing with LUB32 control circuit Load type 3-phase motor - cooling: self-cooled Tripping threshold 14.2 x Ir +/- 20 % Aug 11, 2019 1 The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. Ui rated insulation voltage 600 V conforming to CSA C22.2 No 14 600 V conforming to UL 508 690 V conforming to IEC 60947-1 Uimp rated impulse withstand voltage 6 kV conforming to IEC 60947-6-2 Safe separation of circuit 400 V SELV between the control and auxiliary circuits conforming to IEC 60947-1 400 V SELV between the control or auxiliary circuit and the main circuit conform- ing to IEC 60947-1 Product weight 0.3 lb(US) (0.135 kg) Environment Heat dissipation 2 W control circuit with LUB12 3 W control circuit with LUB32 Immunity to microbreaks 3 ms Immunity to voltage dips 70 % 500 ms conforming to IEC 61000-4-11 Standards CSA C22.2 No 14 type E EN 60947-6-2 IEC 60947-6-2 UL 508 type E with phase barrier Product certifications DNV ATEX UL ABS GL GOST ASEFA LROS (Lloyds register of shipping) BV CSA CCC IP degree of protection IP20 front panel and wired terminals conforming to IEC 60947-1 IP20 other faces conforming to IEC 60947-1 IP40 front panel outside connection zone conforming to IEC 60947-1 Protective treatment TH conforming to IEC 60068 Ambient air temperature for operation -13...158 F (-25...70 C) Ambient air temperature for storage -40...185 F (-40...85 C) Operating altitude 6561.68 ft (2000 m) Fire resistance 1202 F (650 C) conforming to IEC 60695-2-12 1760 F (960 C) parts supporting live components conforming to IEC 60695-2-12 Shock resistance 10 gn power poles open conforming to IEC 60068-2-27 15 gn power poles closed conforming to IEC 60068-2-27 Vibration resistance 2 gn 5...300 Hz power poles open conforming to IEC 60068-2-6 4 gn 5...300 Hz power poles closed conforming to IEC 60068-2-6 Resistance to electrostatic discharge 8 kV level 3 in open air conforming to IEC 61000-4-2 8 kV level 4 on contact conforming to IEC 61000-4-2 Non-dissipating shock wave 1 kV serial mode conforming to IEC 60947-6-2 2 kV common mode conforming to IEC 60947-6-2 Resistance to radiated fields 9.14 V/yd (10 V/m) 3 conforming to IEC 61000-4-3 Resistance to fast transients 2 kV class 3 serial link conforming to IEC 61000-4-4 4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4 Immunity to radioelectric fields 10 V conforming to IEC 61000-4-6 Ordering and shipping details Category 22397 - TESYS U - CNTRL MOD(LUCA,LUCD) Discount Schedule I11 GTIN 00785901221913 Nbr. of units in pkg. 1 Package weight(Lbs) 0.28000000000000003 Returnability Y Country of origin FR 2