The UPA 130 Power Alert reduces the risk of electrical arc flash by pre-verifying the electrical isolation from outside of a control panel . Hard wired to the circuit breaker or main disconnect, the UPA flashes whenever voltage is present . Engineered with redundant circuitry, the Power Alert is powered by the same voltage that it indicates . OPERATION The eight detector UPA-130 visually alerts to the presence of dangerous AC or DC (Store Energy) potentials occurring between any combination of the four monitored input lines (L1, L2, L3, GND) . Two LED indicators are assigned to each input line and are designated and . For each input line carrying an AC potential (bi-polar) , both the and LEDs UL TYPE IND . CONT . EQ . will be active . A DC or Stored Energy potential will illuminate the 4X, 12, 13 496Y LED for the positive line and the LED for the negative line . The UPA-130 Series is UL Listed under UL File Number E55826 . 30mm Universal Power Alert Verification of Stored Energy Inside A Panel Redundant Circuitry Fits 30mm Knockout 40-750 VAC, 30-1000 VDC SPECIFICATIONS OPERATIONAL RANGE AC SINGLE OR 3-PHASE 40 to 600 VAC, 50/60/400 Hz, (LINE-TO-LINE or LINE-TO-GND DC OR STORED ENERGY 30 to 1000 VDC, (LINE-TO-LINE or LINE-TO-GND) MAXIMUM RATED 750 VAC/1000 VDC (LINE-TO-LINE or LINE-TO-GND) VOLTAGE DETECTION THRESHOLDS 29 VAC 3-Phase, 40 VAC SINGLE-Phase, 27 VDC (TYP CUTOFF) POWER CONSUMPTION 12 W . atts 750 VAC (Approximately) TEMPERATURE RATING Operate -4 to 131F (-20 to +55C) Storage -40 to 185F (-40 to +85C) ENCLOSURE Totally Encapsulated for Environment Protection TERMINATIONS (4) 8 ft, 18 AWG 1000V, RED YEL BLU GRN/YEL UL-1452 L1 L2 L3 GRD WEIGHT 7 oz . ORDERING INFORMATION INDICATOR FLASH RATES (L1, L2, L3, GND) 3- Phase Line-To-Line (VAC) <29 30 120 240 480 600 750 MODEL NUMBER DESCRIPTION Flashes/Sec (Typical) 0 13 . 4 .2 58 . 73 . 80 . 8 .8 UPA-130 30mm Universal Power Alert DC or Stored Energy (VDC) <27 30 48 110 300 600 1000 UPA-130-DIV2 Class I, Div 2 Flashes/Sec (Typical) 0 1 .6 25 . 45 . 6 .9 88 . 91 . UPA-130S Solid ON GND DETECTOR THRESHOLDS (LEAKAGE ANY PHASE-TO-GROUND) UPA-130-GOV Amber LED 3- Phase Line-To-Line (VAC) 30 120 240 480 750 Accessories L1, L2, or L3 To Ground Continuity (OHMS) 2M 2M 3M 5M 7M UPA-WP130 ANSI Warning Plate Detector Included Fault Current (A) 7 26 38 60 67 UPA-BZL Flush Mounting Kit for UPA-130 Series DETECTOR INCLUDED FAULT CURRENT (PHASE-TO-GROUND SHORT) Flash 1-1/4 knockout 3- Phase Line-To-Line (VAC) 30 120 240 480 750 0 OHM Phase-To-Ground Current (A) 28 108 219 455 730 220 Diversified Electronics 800.727.5646 atcdiversified.com Diversified Electronics 800.727.5646 atcdiversified.com POWER ALERTS UPA-130 SeriesX-ON Electronics Largest Supplier of Electrical and Electronic Components Click to view similar products for Test Accessories - Other category: Click to view products by Mueller manufacturer: Other Similar products are found below : AO1026 AO1035 AO1051 AO1059 149116 149118 RS40 RS41 AO1030 AO1032 AO1036 AO1058 4742 KTS288540 11-32-2733 00415 00163 PACC-ZD005 700M20TH 628824000 MPT-VF B3 15010A0A0100M0 B3 15050A0D01A2M0 B3 15060A0D0100M0 98- CAL020 MO-SCREEN VDV500-705 68-020-01P CVRF02 CPAK8 RT-ZA19 LCR-OPT-02 1-1437358-1 DME D110 T1 LMLH 50 FLUKE PM9082/001 85392-12 ST18/SMAM/SMAM/72 HO720 45025 45028 CT2300 CC545 VT-1000 CT3041 VS-AVT-CABLE-08 6172A 68-023-01 67-023-01 67-012-01